| Port | Protocol / platform |
|---|---|
| UDP 47808 | BACnet/IP (0xBAC0). The standard. Sites with multiple BACnet networks sometimes use 47809 and up. |
| TCP 502 | Modbus TCP. Wireshark's dissector is bound to this port — on anything else you need Decode As. |
| TCP 802 | Modbus over TLS. Less common but part of the spec. |
| TCP 4840 | OPC UA. Not a hard default — confirm the endpoint URL with the server owner. |
| TCP 1911 | Niagara Fox, unencrypted. Should not be exposed to the internet. |
| TCP 4911 | Niagara FoxS, TLS-secured. The modern expectation. |
| TCP 443 | BACnet/SC and general HTTPS. SC rides WebSockets over TLS. |
| TCP 80 / 443 | Device and gateway web configuration interfaces. |
| UDP 161 / 162 | SNMP and SNMP traps — common on power meters and network gear. |
| TCP 22 | SSH. Sometimes the only way into a JACE or a Linux-based gateway. |
| TCP 21 | FTP. Still found on older gateways for configuration upload. |
| UDP 67 / 68 | DHCP. Relevant when a controller unexpectedly changes address. |
| UDP 123 | NTP. Matters more than people expect — OPC UA fails on clock drift. |
How to use it
- Use this when requesting firewall rules — IT will want the specific port and transport.
- Also useful in reverse: if a scan shows one of these open, you know what's running.
- Always confirm against the actual device. Ports are configurable and plenty of sites don't use defaults.
Background reading: Chapters 19–20 — networking →