How to use it
- Measure line-to-line voltage at the motor and clamp each leg; enter the average current.
- Use the drive's reported power factor if you have it. Across-the-line motors at full load sit around 0.85–0.90; lightly loaded, much lower.
- Compare the % of nameplate FLA to what the sequence says the motor should be doing. A fan commanded to full speed pulling 60% FLA is not moving design air.
- On a VFD, current — not voltage — tracks load. A drive holds volts-per-hertz roughly constant, so a half-speed motor still sees near-nameplate voltage while its amps drop.
Practice reading amps against nameplate in the simulator →
Voltage present does not mean the circuit can do work. A motor can sit at 480 V on all three legs and draw almost nothing because it is uncoupled, the load is gone, or a belt is off. The clamp tells you what the voltmeter can't.