| Code | Meaning and what to check |
|---|---|
| 01 | Illegal Function — the device doesn't support that function code. Most often you used FC03 on an input register or FC04 on a holding register. Check the register map. |
| 02 | Illegal Data Address — the address doesn't exist on this device. Usually an off-by-one between conventional address and offset, or a register that only exists on a different model. |
| 03 | Illegal Data Value — the value is out of range for that register, or the quantity requested exceeds what the device allows in one transaction. |
| 04 | Slave Device Failure — an unrecoverable error inside the device while processing the request. |
| 05 | Acknowledge — request accepted but will take a long time. The master should poll for completion rather than time out. |
| 06 | Slave Device Busy — device is processing a long command. Retry later. |
| 08 | Memory Parity Error — used with file record functions; indicates a parity error in the device's memory. |
| 0A | Gateway Path Unavailable — a gateway could not allocate a path. Usually means the gateway is misconfigured. |
| 0B | Gateway Target Failed to Respond — the gateway is fine, the downstream device isn't answering. Check the field side, not the gateway. |
How to use it
- When a request fails, the slave returns the original function code plus 0x80 — so a failed FC03 comes back as 0x83.
- The byte after that is the exception code below.
- Codes 01, 02 and 03 cover the vast majority of what you'll see in the field.