Troubleshooting Matrix
From Chapter 39 of BAS Field Fundamentals: A Field Guide for the New Technician
BAS Field Referencebasfieldreference.com
Symptom → where to start
| Symptom | Start here |
|---|---|
| No BAS value at all | Network, controller, wiring, sensor power |
| BAS value present but incorrect | Sensor, input scaling and type, wiring, terminal |
| Value correct at the device, wrong on the graphic | Wiring, terminal assignment, scaling, point mapping |
| Command present, equipment off | Output, interface device, safety string, electrical path, equipment |
| Command absent when it should be present | Sequence, mode, setpoint, schedule, override, lockout |
| Feedback disagrees with command | Sensor, wiring, interface, mechanical position |
| Actuator says 100%, result is wrong | Physical actuator, coupling, linkage, damper or valve, mechanical restriction |
| VFD fault | Fault history first, then mechanical load, then parameters |
| Equipment runs but produces no result | Mechanical: flow, rotation, belt, coil, capacity |
| Multiple zones affected at once | Stop at the zones. Upstream air handler, static pressure, supply temperature, plant |
| One zone affected, neighbours fine | That box, that room, that sensor |
| Loop oscillates | Sensor noise, actuator stroke time, mechanical binding — tuning last |
| Loop never reaches setpoint | Capacity, then authority, then integral action |
| Alarm firing but nothing is wrong | Threshold, time delay, deadband, suppression logic |
| Works in HAND, not in AUTO | Control path: output, interface relay, safeties, mode, override |
| Intermittent, cannot reproduce | Trend it and come back. Do not guess |
| BAS looks entirely normal, building does not | Go verify physically. The graphic is the last thing to trust |
The layer stack
BAS software → Controller → Signal → Interface device → Electrical circuit → Mechanical equipment → Physical result
Identify the layer first. Half-split within it second. Test third.
The free checks, in order
- Is it in AUTO? HOA switches, drive keypad mode, software auto/manual.
- Is there an override? At any priority, from any source, placed by anyone.
- What mode is it in? Occupied, unoccupied, warm-up, emergency, holiday schedule.
- Are the neighbours affected? One or many decides whether you work here or upstream.
- Has anything changed? Renovation, power event, controller swap, another contractor.
- Is anything alarming that you have not read? Including recently cleared.
- Does the trend show when it started? A start time is a huge clue.
Every one of those is free and takes seconds. Together they resolve or redirect a large share of calls before a tool comes out of the bag.
© 2026 Scott Draper. Free to print and share with your crew.More free tools and cards: basfieldreference.com