Signal Types Quick Reference
From Appendix A of BAS Field Fundamentals: A Field Guide for the New Technician
BAS Field Referencebasfieldreference.com
Analog and discrete signals
| Signal | Expected range | Meter setting | Where to measure | Common failure modes | Caution |
|---|---|---|---|---|---|
| 0–10 VDC | 0–10 V linear | DC volts | Signal to signal-common, at controller and at the device | Voltage drop on long runs; loose terminal; noise from nearby line voltage | Confirm scaling is truly linear; measure at both ends |
| 2–10 VDC | 2–10 V | DC volts | Same | Same as above | 2 V is a valid zero; 0 V means a dead wire |
| 4–20 mA | 4–20 mA | mA DC, meter in series | Break the loop, or across a known loop resistor | Broken conductor; failed transmitter; lost loop power | 0 mA is a broken loop, not a zero. Know if loop-powered or externally powered |
| 0–20 mA | 0–20 mA | mA DC in series | Same | Same | Cannot distinguish true zero from a break — avoid on anything critical |
| Dry contact | Open / closed | Continuity or ohms | Across the contact, power off | Corroded contacts; vibration dropout; wrong NO/NC expectation | Confirm whether the input expects NO or NC |
| Thermistor | Per curve; 10K types ≈ 10K Ω at 77 °F | Ohms, power off, one leg lifted | Across the sensor leads | Drift; open element; wrong type configured | 10K Type II vs III differ badly at range ends |
| RTD | Pt100 = 100 Ω, Pt1000 = 1000 Ω at 0 °C | Ohms, power off | Across the sensor; 3-wire cancels lead resistance | Open element; lead resistance on long 2-wire runs | Nickel and Balco 1K have different curves |
| Thermocouple | Millivolts DC | mV DC | Across the junction leads | Junction corrosion; extension wire of the wrong alloy | Poor resolution on a general-purpose DMM |
| 24 VAC control | ~24 VAC | AC volts | To transformer common, loaded | Overloaded transformer; open fuse; shared-common errors | Unloaded voltage proves nothing |
| Triac output | Switched AC | AC volts, LoZ | Across the load, load connected | Leakage voltage when off; failed triac | A high-impedance meter reads full voltage on an off triac |
| Pulse / contact pulse | Contact closures | Continuity, or pulse count | Across the contact | Bouncing contacts; wrong scaling in software | Units-per-pulse lives in software, not the device |
Communication buses
Once points arrive over a bus, there is nothing to measure with a meter and the questions change.
| Bus | Physical layer | Typical use | What replaces the meter test |
|---|---|---|---|
| BACnet MS/TP | RS-485 twisted pair, daisy chain | Field bus to terminal controllers | MAC address, baud rate, max master, termination, biasing, polarity |
| BACnet/IP | Ethernet | Building controllers to supervisor | IP, subnet, BBMD, device instance |
| Modbus RTU | RS-485 twisted pair | Meters, VFDs, generators, PLCs | Slave address, baud, parity, register map, byte order |
| Modbus TCP | Ethernet | Same, over IP | IP, unit ID, register map |
| LonWorks | FT-10 twisted pair | Older installed base | Neuron ID, bindings, commissioning records |
| EtherNet/IP, PROFINET | Ethernet | PLCs and industrial equipment | Vendor tooling; usually reached through a gateway |
RS-485 basics: it is a daisy chain, not a star. Every device is polarity-sensitive. It needs termination at each physical end and biasing somewhere on the segment. One miswired device, one star branch, or one missing terminator can destabilise an entire bus in ways that look like random dropouts.