Signal Types Quick Reference

From Appendix A of BAS Field Fundamentals: A Field Guide for the New Technician

BAS Field Referencebasfieldreference.com

Analog and discrete signals

SignalExpected rangeMeter settingWhere to measureCommon failure modesCaution
0–10 VDC0–10 V linearDC voltsSignal to signal-common, at controller and at the deviceVoltage drop on long runs; loose terminal; noise from nearby line voltageConfirm scaling is truly linear; measure at both ends
2–10 VDC2–10 VDC voltsSameSame as above2 V is a valid zero; 0 V means a dead wire
4–20 mA4–20 mAmA DC, meter in seriesBreak the loop, or across a known loop resistorBroken conductor; failed transmitter; lost loop power0 mA is a broken loop, not a zero. Know if loop-powered or externally powered
0–20 mA0–20 mAmA DC in seriesSameSameCannot distinguish true zero from a break — avoid on anything critical
Dry contactOpen / closedContinuity or ohmsAcross the contact, power offCorroded contacts; vibration dropout; wrong NO/NC expectationConfirm whether the input expects NO or NC
ThermistorPer curve; 10K types ≈ 10K Ω at 77 °FOhms, power off, one leg liftedAcross the sensor leadsDrift; open element; wrong type configured10K Type II vs III differ badly at range ends
RTDPt100 = 100 Ω, Pt1000 = 1000 Ω at 0 °COhms, power offAcross the sensor; 3-wire cancels lead resistanceOpen element; lead resistance on long 2-wire runsNickel and Balco 1K have different curves
ThermocoupleMillivolts DCmV DCAcross the junction leadsJunction corrosion; extension wire of the wrong alloyPoor resolution on a general-purpose DMM
24 VAC control~24 VACAC voltsTo transformer common, loadedOverloaded transformer; open fuse; shared-common errorsUnloaded voltage proves nothing
Triac outputSwitched ACAC volts, LoZAcross the load, load connectedLeakage voltage when off; failed triacA high-impedance meter reads full voltage on an off triac
Pulse / contact pulseContact closuresContinuity, or pulse countAcross the contactBouncing contacts; wrong scaling in softwareUnits-per-pulse lives in software, not the device

Communication buses

Once points arrive over a bus, there is nothing to measure with a meter and the questions change.

BusPhysical layerTypical useWhat replaces the meter test
BACnet MS/TPRS-485 twisted pair, daisy chainField bus to terminal controllersMAC address, baud rate, max master, termination, biasing, polarity
BACnet/IPEthernetBuilding controllers to supervisorIP, subnet, BBMD, device instance
Modbus RTURS-485 twisted pairMeters, VFDs, generators, PLCsSlave address, baud, parity, register map, byte order
Modbus TCPEthernetSame, over IPIP, unit ID, register map
LonWorksFT-10 twisted pairOlder installed baseNeuron ID, bindings, commissioning records
EtherNet/IP, PROFINETEthernetPLCs and industrial equipmentVendor tooling; usually reached through a gateway

RS-485 basics: it is a daisy chain, not a star. Every device is polarity-sensitive. It needs termination at each physical end and biasing somewhere on the segment. One miswired device, one star branch, or one missing terminator can destabilise an entire bus in ways that look like random dropouts.