There is a category of fault that will never page you, never show red on a graphic, and never generate a complaint. Occupants are comfortable. Equipment runs. Every point reads normal. And the building is burning a substantial share of its energy budget heating air it just finished cooling.
Simultaneous heating and cooling is the most expensive fault most technicians never look for, precisely because nothing in the system is designed to tell you about it. Comfort is the metric the BAS was built to defend, and comfort is being delivered. The waste is invisible by design.
Finding it: the three-day trend
You don't need analytics software or an energy audit to find this. You need three points and a weekend.
What to trend
- Heating valve command (or reheat output)
- Cooling valve command
- Discharge air temperature
Set the interval to five minutes and let it run for three days. Five minutes is fast enough to catch real overlap and slow enough that three days of data stays manageable. Three days gets you at least one occupied/unoccupied cycle and, if you're lucky, a weekend.
What you're looking for
Any period where both valves show open at the same time for more than about fifteen minutes. Brief overlap during a changeover is normal and expected. Sustained overlap is not — that's the building actively working against itself.
The four causes, in order of how often you'll find them
Valve scaling inverted
The valve reads 100% when it is actually closed, or 0% when it is actually open. The loop is behaving correctly and the feedback is lying about it. This is the most common cause and the easiest to confirm: command the valve to a known position and physically look at the stem.
Normally-open programmed as normally-closed
A normally-open valve wired and programmed as if it were normally-closed sits fully open at zero signal. Everything about the sequence looks right on screen. The valve has simply been passing hot water since commissioning.
No deadband between heating and cooling
If the heating loop's upper limit and the cooling loop's lower limit touch — or overlap — the zone will chase itself around setpoint with both outputs modulating. A small deadband between the two is what stops this, and it is very often missing or set to zero.
Valve leaking through
Mechanical, not a controls problem, but it lands on your ticket anyway. A valve commanded fully closed that still passes flow will produce exactly this signature. Discharge air temperature is what separates this from the three causes above.
Why commissioning didn't catch it
This is worth understanding, because it explains why the fault is so widespread in buildings that were properly commissioned.
Commissioning and test-and-balance typically verify a sample of units — often somewhere in the range of a third of the installed equipment, not all of it. On a building with two hundred VAV boxes, that leaves a lot of boxes nobody ever functionally tested. If a valve was scaled backwards at the factory or programmed wrong from a copied template, it goes into service that way and stays that way.
What to do when you find it
| Evidence | Most likely cause | First action |
|---|---|---|
| Both valves commanded open, sustained | Missing or zero deadband | Check the loop setpoints and separation between heating and cooling |
| Valve command and physical position disagree | Scaling inverted or NO/NC mismatch | Command to a known position and physically verify the stem |
| Both commanded closed, discharge air still rising | Valve leaking through | Mechanical — the valve needs service or replacement |
| One box only | Individual configuration error | Fix it, then check boxes configured from the same template |
| Many boxes, same signature | Template copied with the error in it | Fix the template, then re-verify every box built from it |
The bigger lesson
Everything about this fault is a specific case of a general problem: the front end reports what it was told, not what is happening. Both valve points are “working.” Both loops are “correct.” The graphic is green. And the actual physical reality — hot water and chilled water meeting in the same duct — appears nowhere on any screen because no single point describes it.
The habit worth building isn't memorising this one fault. It's asking, on any system you inherit, which physical realities have no point representing them — and then trending your way to an answer.